Select the unit model:

Enter calculation values :

  Supply Extract
Airflow:  l/s  l/s

Duct pressure:

 Pa  Pa

 

Place:
 

Design temperature:  °C
Exhaust air temperature limit:  °C
Supply air target temperature :  °C
Extract air temperature:  °C

Enter the target information:

Handler:
Date:
Target:
 
Name:
Street address:
Postcode:
Post office:
Project:
Positio:
Additional information:

Results:

Results at the calculation point : Supply: Extract:
Fan speed: 44 % 39 %
Air flow: 40 l/s 40 l/s
Total pressure: 28 Pa 27 Pa
Air speed: 2.0 m/s 1.99 m/s
Input power: 16 W 13 W
Annual fan energy consumption 251 kWh
SFP value: 0.71 kW/(m³/s)

 
Plate heat exchanger: Supply: Extract:
Pressure drop: 36 Pa 36 Pa
Efficiency with equal airflows: 84.4 %
Supply air temperature after the heat exhanger 13.7 °C
Postheating demand at the calculation point: 113 W
Off
On
Temperature after preheating: -
Preheating power: -

 
DIVK sound values at the calculation point Lw LwA
Supply air duct: 61.9 dB 54.2 dB(A)
Extract air duct: 57.4 dB 34.4 dB(A)
Soundpressure level in the room
(10m² absorbtion LpA)
22.0 dB(A)

 

SPL-levels by the octavebands
631252505001k2k4k8kdBdB(A)
Through the casing to the room4437322218129146.426.0
Supply585549525049423461.954.2
Extract41383930322113457.434.4
* The sound level of the measurement does not exceed the background noise level

 
Calculation of annual efficiency:
Exhaust air temperature: -18.7 °C
Exhaust air temperature limit 0 °C
Air flow ratio supply / extract 1.00
Amount of energy required for ventilation: 6351 kWh
Achieved energy saving: 4940 kWh
Total energy consumption for ventilation 1411 kWh
HRV annual efficiency: 77.8 %