Results:

Results at the calculation point : Supply: Extract:
Fan speed: 45 % 43 %
Air flow: 40 l/s 40 l/s
Total pressure: 37 Pa 43 Pa
Air speed: 3.3 m/s 3.26 m/s
Input power: 17 W 16 W
Annual fan energy consumption 289 kWh
SFP value: 0.82 kW/(m³/s)

 
Plate heat exchanger: Supply: Extract:
Pressure drop: 36 Pa 36 Pa
Efficiency with equal airflows: 84.4 %
Supply air temperature after the heat exhanger 13.7 °C
Postheating demand at the calculation point: 113 W
Off
On
Temperature after preheating: -
Preheating power: -

 
DIVK sound values at the calculation point Lw LwA
Supply air duct: 60.0 dB 51.9 dB(A)
Extract air duct: 52.6 dB 31.6 dB(A)
Soundpressure level in the room
(10m² absorbtion LpA)
24.0 dB(A)

 

SPL-levels by the octavebands
631252505001k2k4k8kdBdB(A)
Through the casing to the room4540352119129053.328.0
Supply565546474747413160.051.9
Extract35433726292013252.631.6
* The sound level of the measurement does not exceed the background noise level

 
Calculation of annual efficiency:
Exhaust air temperature: -18.7 °C
Exhaust air temperature limit 0 °C
Air flow ratio supply / extract 1.00
Amount of energy required for ventilation: 6351 kWh
Achieved energy saving: 4940 kWh
Total energy consumption for ventilation 1411 kWh
HRV annual efficiency: 77.8 %