Select the unit model:

Enter calculation values :

  Supply Extract
Airflow:  l/s  l/s

Duct pressure:

 Pa  Pa

 

Place:
 

Design temperature:  °C
Exhaust air temperature limit:  °C
Supply air target temperature :  °C
Extract air temperature:  °C

Enter the target information:

Handler:
Date:
Target:
 
Name:
Street address:
Postcode:
Post office:
Project:
Positio:
Additional information:

Results:

Results at the calculation point : Supply: Extract:
Fan speed: 63 % 56 %
Air flow: 40 l/s 40 l/s
Total pressure: 43 Pa 42 Pa
Air speed: 3.3 m/s 3.26 m/s
Input power: 23 W 19 W
Annual fan energy consumption 366 kWh
SFP value: 1.04 kW/(m³/s)

 
Plate heat exchanger: Supply: Extract:
Pressure drop: 43 Pa 43 Pa
Efficiency with equal airflows: 83.5 %
Supply air temperature after the heat exhanger 13.2 °C
Postheating demand at the calculation point: 134 W
Off
On
Temperature after preheating: -
Preheating power: -

 
DIVK sound values at the calculation point Lw LwA
Supply air duct: 65.0 dB 59.3 dB(A)
Extract air duct: 55.7 dB 42.2 dB(A)
Soundpressure level in the room
(10m² absorbtion LpA)
26.9 dB(A)

 

SPL-levels by the octavebands
631252505001k2k4k8kdBdB(A)
Through the casing to the room50434025162**51.730.9
Supply615452555852413565.059.3
Extract46464539412914*55.742.2
* The sound level of the measurement does not exceed the background noise level

 
Calculation of annual efficiency:
Exhaust air temperature: -18.2 °C
Exhaust air temperature limit 0 °C
Air flow ratio supply / extract 1.00
Amount of energy required for ventilation: 6351 kWh
Achieved energy saving: 4904 kWh
Total energy consumption for ventilation 1447 kWh
HRV annual efficiency: 77.2 %

Additional information

Return
Error messages
 

Created:October 04 2023 14:55:41