Select the unit model:

Enter calculation values :

  Supply Extract
Airflow:  l/s  l/s

Duct pressure:

 Pa  Pa

 

Place:
 

Design temperature:  °C
Exhaust air temperature limit:  °C
Supply air target temperature :  °C
Extract air temperature:  °C

Enter the target information:

Handler:
Date:
Target:
 
Name:
Street address:
Postcode:
Post office:
Project:
Positio:
Additional information:

Results:

Results at the calculation point : Supply: Extract:
Fan speed: 55 % 44 %
Air flow: 40 l/s 40 l/s
Total pressure: 48 Pa 33 Pa
Air speed: 1.6 m/s 1.63 m/s
Input power: 18 W 13 W
Annual fan energy consumption 277 kWh
SFP value: 0.79 kW/(m³/s)

 
Plate heat exchanger: Supply: Extract:
Pressure drop: 28 Pa 28 Pa
Efficiency with equal airflows: 61.6 %
Supply air temperature after the heat exhanger 3.0 °C
Postheating demand at the calculation point: 632 W

 
DIVK sound values at the calculation point Lw LwA
Supply air duct: 56.6 dB 45.7 dB(A)
Extract air duct: 52.1 dB 37.7 dB(A)
Soundpressure level in the room
(10m² absorbtion LpA)
32.8 dB(A)

 

SPL-levels by the octavebands
631252505001k2k4k8kdBdB(A)
Through the casing to the room50514237291512*53.436.8
Supply484844454139291856.645.7
Extract4645443924257*52.137.7
* The sound level of the measurement does not exceed the background noise level

 
Calculation of annual efficiency:
Exhaust air temperature: -8.0 °C
Exhaust air temperature limit 0 °C
Air flow ratio supply / extract 1.00
Amount of energy required for ventilation: 6351 kWh
Achieved energy saving: 3858 kWh
Total energy consumption for ventilation 2493 kWh
HRV annual efficiency: 60.7 %

Additional information

Return
Error messages
 

Created:October 04 2023 14:55:41