Supply | Extract | |
Airflow: | l/s | l/s |
Duct pressure: |
Pa | Pa |
Place:
Design temperature: | °C |
Exhaust air temperature limit: | °C |
Supply air target temperature : | °C |
Extract air temperature: | °C |
Handler: | |
Date: | |
Target: | |
Name: | |
Street address: | |
Postcode: | |
Post office: | |
Project: | |
Positio: | |
Additional information: |
Results at the calculation point : | Supply: | Extract: |
Fan speed: | 55 % | 44 % |
Air flow: | 40 l/s | 40 l/s |
Total pressure: | 48 Pa | 33 Pa |
Air speed: | 1.6 m/s | 1.63 m/s |
Input power: | 18 W | 13 W |
Annual fan energy consumption | 277 kWh | |
SFP value: | 0.79 kW/(m³/s) |
Plate heat exchanger: | Supply: | Extract: |
Pressure drop: | 28 Pa | 28 Pa |
Efficiency with equal airflows: | 61.6 % | |
Supply air temperature after the heat exhanger | 3.0 °C | |
Postheating demand at the calculation point: | 632 W |
DIVK sound values at the calculation point | Lw | LwA |
Supply air duct: | 56.6 dB | 45.7 dB(A) |
Extract air duct: | 52.1 dB | 37.7 dB(A) |
Soundpressure level in the room (10m² absorbtion LpA) |
32.8 dB(A) |
SPL-levels by the octavebands | ||||||||||
63 | 125 | 250 | 500 | 1k | 2k | 4k | 8k | dB | dB(A) | |
Through the casing to the room | 50 | 51 | 42 | 37 | 29 | 15 | 12 | * | 53.4 | 36.8 |
Supply | 48 | 48 | 44 | 45 | 41 | 39 | 29 | 18 | 56.6 | 45.7 |
Extract | 46 | 45 | 44 | 39 | 24 | 25 | 7 | * | 52.1 | 37.7 |
* The sound level of the measurement does not exceed the background noise level |
Calculation of annual efficiency: | ||
Exhaust air temperature: | -8.0 °C | |
Exhaust air temperature limit | 0 °C | |
Air flow ratio supply / extract | 1.00 | |
Amount of energy required for ventilation: | 6351 kWh | |
Achieved energy saving: | 3858 kWh | |
Total energy consumption for ventilation | 2493 kWh | |
HRV annual efficiency: | 60.7 % |